Thông số sản phẩm
1Phase Power Options:
6 / 10 / 20 / 30 /40 kW
3Phase Power Options:
10 / 20 / 30 / 40 / 60 / 80 / 100 kW
Over Load Capacity:
10 min for 110%
Isolation Voltage:
2.500 VAC (Input-Output, Input-Chassis, Output-Chassis)
Grid DC Connection:
Sequence Rail Terminal (+/- DC)
Input DC Voltage, MPPT:
300-350 VDC (1 Phase)
Min-Max Input DC Voltage:
250-450 (1 Phase)
Input Protection:
Thermic Over Current Fuse With Indicator, Over Voltage and EMI-RFI Filter
Instant Voltage and Pulse Protection:
IEEE 587 (4500 A, 110 Joules)
Output Voltage:
220/230 VAC (1 Phase)
Output Voltage Tolerance:
±
Output Frequency:
50 &ndash
Output Frequency Tolerance:
±
Output Waveform:
Fully Sinusoidal, THD <
Output Protection:
Short Circuit, Over Current, Over Voltage and Over Temperature
Output Transformer:
Galvanically Isolated
Grid Number 1 Phase:
12 Grid In Series, MPPT Grid Voltage 26-28 VDC, 10 Grid In Series, MPPT Grid Voltage 33-36VDC
Grid Number 3 Phase:
20 Grid In Series, MPPT Grid Voltage 26-28 VDC, 16 Grid In Series, MPPT Grid Voltage 33-36VDC
Indicator and Buttons:
Graphic LCD Panel, Menu Select and Menu Set Buttons
Warning Messages:
Input Fuse/Operating Mode/Inverter Synchronization/DC Input High- Low/Inverter Over Load/Internal Over Temperetaure /Inverter Over Temperature/IGBT SCR Fuse Fail/Inverter Output High-Low
Viewing Measured Values:
Output Voltage/Output Frerquency/Inverter Load Level/DC Bus Voltage/Internal Temperature /Event History
Adjusting Parameters:
Date/Time /Alarm Sound Level/Communication Slave Number/Led Test
Sound Alarm:
On Warning Messages 2 Short &lsquo
Communication:
RS 485 &ndash
Access to Cabin:
Front Access
Level of protection:
IP 21 as Standard
Permitted temperature range:
<
Maximum height above sea level: